40.5kV Solid Insulated Switchgear
Or email sales@banglamark.com.bd

Or email sales@banglamark.com.bd
This shielded solid insulated switchgear is used in power supply systems with a rated voltage of 35 kV, AC 50 Hz, and for terminal power supply. It complies with IEC 298 and is used in power grids, factory distribution, high voltage transmission, railways, urban power distribution and wind power generation.
Solid Insulation
A shielding layer of conductive material keeps the whole surface at earth potential, so it is safe if touched accidentally. The entire circuit is insulated with epoxy and silicone rubber, leaving no live parts in free air. As a result it is less affected by dirt, humidity and pollution, and needs less maintenance. Each phase is self-contained in a single epoxy block, which greatly reduces phase-to-phase discharge and the risk of internal arc faults.
Modular architecture
The modular architecture reduces switchgear size. The solid insulated switchgear measures 700 × 2000 × 1150, only 1/6 of a traditional air insulated type such as KYN61.
Optimized Electric Field
Computer simulation is used to optimise the electric field and insulation design.
Safety
Live parts sealed to IP67.
Inner-cone cable terminals improve connection reliability.
Extreme Environment Application
Suitable for cold, high-altitude, humid, corrosive, low-lying and explosion-hazard areas.
| Parameter Title | Unit | Vacuum Circuit Breaker | Disconnecting Switch | Earthing Switch |
|---|---|---|---|---|
| Rated Voltage | kV | 40.5 | 40.5 | 40.5 |
| Arc Quenching | - | Vacuum | - | - |
| Rated Current | A | 1250 | 1250 | 1250 |
| Rated Frequency | Hz | 50/60 | 50/60 | 50/60 |
| Main Circuit Resistance | μΩ | ≤120 | ≤120 | ≤120 |
| Power Frequency Withstand Voltage(1 min) | kV | 118 | 118 | 118 |
| Lightning Impulse Withstand Voltage | kV | 215 | 215 | 215 |
| Rated Short-circuit Breaking Current | kA | 31.5 | - | - |
| Breaking Times | times | 30 | - | - |
| Rated Short-circuit Making Current | kA | 80 | - | - |
| Rated Short-time Withstand Current/ Duration | kA/S | 31.5/4s | 31.5/4s | 31.5/4s |
| Rated Peak Withstand Current | kA | 80 | 80 | 80 |
| Internal Arcing Test (AFLR level) | kA/S | 31.5kA/0.5s (including bus compartment, switch compartment, cable compartment) | ||
| Degree of Protection | - | IP67 | IP67 | IP67 |
| Mechanical Endurance | Times | 10000 | 3000 | 3000 |